  • Q39. Where can landing valves be installed in accordance to preference?

    Sunday,2 Aug 2015

    A39.  Landing valves shall be located in accordance to the following preference:

    i.    In fire Fighting lobby (if provided), for the first landing valve.
    ii.   In Fire fighting or exit staircase, for the first landing valve.
    iii.  In smoke free enclosure or external corridor.
    iv.   In the common corridor or area within a protected shaft.

    Hits :  357
  • Q40. What is the length of coverage for one landing valve?

    Sunday,2 Aug 2015

    A40.  Every part of the floor area shall be within 30 m coverage of a landing valve.

    Hits :  1414
  • Q41. When shall an emergency command centre be provided?

    Sunday,2 Aug 2015

    A41.  An Emergency Command Centre shall be provided in any building which is ‘Highrise’ with 23 m or more in height with the exception of One-and-Two-Family Dwelling and such Emergency Command Center shall have the following:

    i.    Fire lift
    ii.   Emergency voice communication system
    iii.  Engineered smoke control system.

    Hits :  976
  • Q42. What is the size requirement for an emergency command centre?

    Sunday,2 Aug 2015

    A42.  An Emergency Command Centre shall be of adequate size to house all the terminals and supervisory/control equipment, etc of the building’s fire protection/detection systems and a free working space of at least 8.9 m2 with no dimension lesser than 2440 mm.

    Hits :  747
  • Q43. Where shall the emergency command centre be located?

    Sunday,2 Aug 2015

    A43.  An Emergency Command Centre shall be located adjacent to the fire lift lobby at the designated storey of the building (i.e. the lobby of the building on the first storey or immediately adjacent thereto)

    Hits :  653
  • Q44. swing direction for doors for fire exits?

    Sunday,2 Aug 2015

    A44.  Doors required to be of the side-hinged or pivoted-swinging type shall swing in the direction of egress travel where serving a room or area with an occupant load of 50 or more. A door shall swing in the direction of egress travel under either of the following conditions:

    i.     Where the door is used in an exit enclosure
    ii.    Where the door serves a high hazard contents area

    Hits :  1471
  • Q45. What is the type of construction for exit staircase shaft based on the height of the building?

    Sunday,2 Aug 2015

    A45.  Exit stairs serving High-rise buildings, Midrise buildings, High depth Underground buildings and buildings connecting four or more stories shall be constructed of RCC (Reinforced Concrete) with a minimum of 2 hour fire rating. Exit Stairs serving Lowrise buildings, Lowdepth Underground buildings and buildings connecting Three or less stories shall be protected with 2 hour fire rated construction.

    Hits :  700
  • Q46. Can spiral stairs be used for egress? \

    Sunday,2 Aug 2015

    A46.  Spiral Stairs is not allowed as a part of means of egress.

    Hits :  976
  • Q47. Can interlocking or scissor stair be treated as 2 staircases?

    Sunday,2 Aug 2015

    A47.  Interlocking or scissor stairs shall be considered only as a single exit.

    Hits :  601
  • Q48. Where shall floor diagrams be provided?

    Sunday,2 Aug 2015

    A48.  A floor diagram shall be provided in staircase landings on the wall beside the exit door. Floor diagrams shall also be provided beside fire alarm panels, in smoke-free enclosures, in fire fighting lobbies and in individual rooms of hotels and health care occupancies.

    Hits :  780
  • Q49. What information shall a floor diagram have?

    Sunday,2 Aug 2015

    A49.  Floor diagrams shall show the actual floor layout, exit stairways locations, corridors, rooms, landing valves, hosereel, fire extinguishers, lift lobbies and other useful information for fire department as well as occupants.

    Hits :  572
  • Q50. What is the mode of ventilation for exit staircases in highrise buildings (23m or more in height)?

    Sunday,2 Aug 2015

    A50.  Every escape staircase serving buildings of 23 m in height or more must be made a smoke proof enclosure. The means of achieving a smoke proof enclosure should be by pressurization.

    Hits :  824
  • Q51. What is the fire rating for a smoke proof enclosure?

    Sunday,2 Aug 2015

    A51.  A smoke proof enclosure shall be enclosed from the highest point to the lowest point by barriers having 2-hour fire resistance ratings.  

    Hits :  653
  • Q52. What is the fire rating requirement for an exit passageway?

    Sunday,2 Aug 2015

    A52.  The exit passageway shall be separated from the remainder of the building by a 2-hour fire resistance rating.

    Hits :  880
  • Q53. What is the required mode of ventilation for non-high rise buildings?

    Sunday,2 Aug 2015

    A53.  Staircase ventilation for non-highrise buildings shall be provided with natural, mechanical ventilation or by providing smoke proof enclosures.

    Hits :  675
  • Q54. What is the egress final discharge requirement for sprinkler protected buildings?

    Sunday,2 Aug 2015

    A54. For sprinkler protected buildings, not more than 50 percent of the required number of exits, and not more than 50 percent of the required egress capacity, shall discharge through areas on the level of exit discharge.

     

    Hits :  571
  • Q55. What is the minimum separation distance between two exits?

    Sunday,2 Aug 2015

    A55.   The minimum separation distance between two exits or exit access doors in a sprinklered building shall be not less than one-third the length of the maximum overall diagonal dimension of the building or area to be served. This distance shall be half the diagonal for non-sprinklered buildings.

    Hits :  1368
  • Q56. minimum clear width of a corridor or passageway?

    Sunday,2 Aug 2015

    A56.  The clear width of any corridor or passageway serving an occupant load of 50 or more shall be not less than 1200 mm.

    Hits :  1948
  • Q57.In what situation is single exit permitted in a non-sprinklered apartment building? \

    Sunday,2 Aug 2015

    A57.  Any non-sprinklered dwelling unit shall be permitted to have a single exit, provided that one of the following criteria is met:

    i.    The dwelling unit has an exit door opening directly to the street or yard at ground level.
    ii.  The dwelling unit has direct access to an outside stair and serves a maximum of two units, both of which are located on the same floor.
    iii. The dwelling unit has direct access to an interior stair that serves only that unit and is separated from all other portions of the building by fire barriers having a minimum 1hour fire resistance rating, with no opening therein.
    iv.  Travel distance from the anywhere in the unit shall not exceed 23m to the final discharge.
    v.   Total floor area is less than 500 m2

    Hits :  787
  • Q58. In what situation is a single exit permitted in a sprinklered apartment building?

    Sunday,2 Aug 2015

    A58.  Any building that is protected throughout by an approved, supervised automatic sprinkler system has four or fewer stories, and has not more than four dwelling units per story shall be permitted to have a single exit, provided that all of the following conditions apply:

    i.    The stairway is separated from the rest of the building by barriers having not less than a 1-hour fire resistance rating, with self-closing 1-hour fire door assemblies protecting all openings between the stairway enclosure and the building.
    ii.    The stairway does not serve more than one-half story below the level of exit discharge. iii.      All corridors serving as access to exits have a minimum 1-hour fire resistance rating. iv.     There is not more than 35 ft (10.7 m) of travel distance from the entrance door of any dwelling unit to the exit staircase
    v.     One-half-hour fire-rated horizontal and vertical separation between dwelling units is provided. vi.     Travel distance from anywhere from the unit to the unit exit door shall not exceed 23m. vi.     Total floor area is less than 500 m2

    Hits :  616

DCD Measures

CONTACT US CONTACT US

Contact Us

x
997
+971 800 997
+971 4 7052041 - 24/7
customer.care@dcd.gov.ae & info@dcd.gov.ae
Arc, P.O. Box 11377 Dubai, UAE
Contact center receives your call 24 X 7 X 365

NEWSLETTER Newsletter

Page last updated 17.01.2023

Site is best viewed in a 1280x1024 screen resolution.

Dubai Smart Government DCD Paperless Government official website اسعاد Dubai Careers

Visitors Counter

546964403
Today
Yesterday
This Week
Last Week
This Month
Last Month
All days
68586
56174
299808
7615159
1007669
2097747
546964403
Your IP: 10.234.102.113
2024-04-18 22:03
  1. Download DCD Smart App
  2. Android App Ios App
 

Application Status

Application Status

smile meter icon dcd
esuggest icon dcd en

123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789 123456

Please Click Here to Listen Highlighted Text

Still need help ?

We are here to provide you with any information or answer any questions you may have

You may also find your answer in our FAQs section