  • Q29. What is the minimum duration of fire fighting water supply for private fire hydrant?

    Sunday,2 Aug 2015

    A29.   Private Fire Hydrant Water supply for fire fighting shall be for 2 hours.

    Hits :  1534
  • Q.30. What is the height limitations for a fire hydrant?

    Sunday,2 Aug 2015

    A30.   The center of a hose outlet shall be not less than 457 mm and not more than 914mm above final grade.

    Hits :  1877
  • Q31. How far shall the distance be between the fire engine access way and any access opening of a building?

    Sunday,2 Aug 2015

    A31.  Access way shall be positioned so that the nearer edge shall be not less than 2 m or more than 10 m from the centre position of the access opening, measured horizontally.

    Hits :  998
  • Q32. What is the gradient requirement for a fire engine access way?

    Sunday,2 Aug 2015

    A32.   Access way shall be laid on a level platform or if on an incline, the gradient shall not exceed 10%.  

    Hits :  890
  • Q33. What is the maximum allowable dead end distance for a fire engine access way?

    Sunday,2 Aug 2015

    A33.  Dead-end access way and fire engine access road shall not exceed 45 m in length or if exceeding 45 m, be provided with turning facilities.

    Hits :  941
  • Q34. What is the minimum height clearance along fire engine access way and access road?

    Sunday,2 Aug 2015

    A34.  Overhead clearance of access way and fire engine access road shall be at least 4.5 m for passage of fire fighting appliances. Overhead obstruction to access way could be entrance gate, link or bridges connecting buildings.

    Hits :  961
  • Q35.In what type of building shall a fire lift be required?

    Sunday,2 Aug 2015

    A35.  In any building which is classified as high-rise or High depth building having more than 2 level of basement, there shall be provided at least one fire lift, which shall be contained within a separate protected shaft or a common protected shaft containing other lifts subject to such other lifts being served at each storey by a fire fighting lobby.  

    Hits :  1450
  • Q36. What is the minimum dimension of a fire lift car?

    Sunday,2 Aug 2015

    A36.  Minimum dimension of a Fire lift car shall be of 1950mm either in length of breadth.

    Hits :  1496
  • Q37. What is the minimum width of a fire fighting staircase?

    Sunday,2 Aug 2015

    A37.   Fire-fighting stairs should be a minimum of 1200 mm wide.

    Hits :  1591
  • Q38. Size requirement for a fire fighting lobby?

    Sunday,2 Aug 2015

    A38.  The fire fighting lobby shall have a clear floor area of not less than 5 m2. The clear floor area should not exceed 20 m2 for spaces serving up to four lifts or 5 m2 per lift for spaces serving more than four lifts.  

    Hits :  1509
  • Q39. Where can landing valves be installed in accordance to preference?

    Sunday,2 Aug 2015

    A39.  Landing valves shall be located in accordance to the following preference:

    i.    In fire Fighting lobby (if provided), for the first landing valve.
    ii.   In Fire fighting or exit staircase, for the first landing valve.
    iii.  In smoke free enclosure or external corridor.
    iv.   In the common corridor or area within a protected shaft.

    Hits :  434
  • Q40. What is the length of coverage for one landing valve?

    Sunday,2 Aug 2015

    A40.  Every part of the floor area shall be within 30 m coverage of a landing valve.

    Hits :  1665
  • Q41. When shall an emergency command centre be provided?

    Sunday,2 Aug 2015

    A41.  An Emergency Command Centre shall be provided in any building which is ‘Highrise’ with 23 m or more in height with the exception of One-and-Two-Family Dwelling and such Emergency Command Center shall have the following:

    i.    Fire lift
    ii.   Emergency voice communication system
    iii.  Engineered smoke control system.

    Hits :  1126
  • Q42. What is the size requirement for an emergency command centre?

    Sunday,2 Aug 2015

    A42.  An Emergency Command Centre shall be of adequate size to house all the terminals and supervisory/control equipment, etc of the building’s fire protection/detection systems and a free working space of at least 8.9 m2 with no dimension lesser than 2440 mm.

    Hits :  899
  • Q43. Where shall the emergency command centre be located?

    Sunday,2 Aug 2015

    A43.  An Emergency Command Centre shall be located adjacent to the fire lift lobby at the designated storey of the building (i.e. the lobby of the building on the first storey or immediately adjacent thereto)

    Hits :  773
  • Q44. swing direction for doors for fire exits?

    Sunday,2 Aug 2015

    A44.  Doors required to be of the side-hinged or pivoted-swinging type shall swing in the direction of egress travel where serving a room or area with an occupant load of 50 or more. A door shall swing in the direction of egress travel under either of the following conditions:

    i.     Where the door is used in an exit enclosure
    ii.    Where the door serves a high hazard contents area

    Hits :  1758
  • Q45. What is the type of construction for exit staircase shaft based on the height of the building?

    Sunday,2 Aug 2015

    A45.  Exit stairs serving High-rise buildings, Midrise buildings, High depth Underground buildings and buildings connecting four or more stories shall be constructed of RCC (Reinforced Concrete) with a minimum of 2 hour fire rating. Exit Stairs serving Lowrise buildings, Lowdepth Underground buildings and buildings connecting Three or less stories shall be protected with 2 hour fire rated construction.

    Hits :  821
  • Q46. Can spiral stairs be used for egress?

    Sunday,2 Aug 2015

    A46.  Spiral Stairs is not allowed as a part of means of egress.

    Hits :  1158
  • Q47. Can interlocking or scissor stair be treated as 2 staircases?

    Sunday,2 Aug 2015

    A47.  Interlocking or scissor stairs shall be considered only as a single exit.

    Hits :  708
  • Q48. Where shall floor diagrams be provided?

    Sunday,2 Aug 2015

    A48.  A floor diagram shall be provided in staircase landings on the wall beside the exit door. Floor diagrams shall also be provided beside fire alarm panels, in smoke-free enclosures, in fire fighting lobbies and in individual rooms of hotels and health care occupancies.

    Hits :  902

DCD Measures

CONTACT US CONTACT US

Contact Us

x
997
+971 800 997
+971 4 7052041 - 24/7
customer.care@dcd.gov.ae & info@dcd.gov.ae
Arc, P.O. Box 11377 Dubai, UAE
Contact center receives your call 24 X 7 X 365

NEWSLETTER Newsletter

Page last updated 10.06.2024

Site is best viewed in a 1280x1024 screen resolution.

Dubai Smart Government DCD Paperless Government official website اسعاد Dubai Careers

Visitors Counter

579286056
Today
Yesterday
This Week
Last Week
This Month
Last Month
All days
25588
92886
323926
39506294
2429640
2468726
579286056
Your IP: 10.234.102.113
2025-05-29 11:28
  1. Download DCD Smart App
  2. Android App Ios App
 

Application Status

Application Status

smile meter icon dcd
esuggest icon dcd en

123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789012345678901234567890123456789012345678901234567890123456789012345678901234567890123456789 123456789 123456

Please Click Here to Listen Highlighted Text

Still need help ?

We are here to provide you with any information or answer any questions you may have

You may also find your answer in our FAQs section